Access Control Wiring & Power: Complete Specification Guide for Commercial Door Hardware (2026)

Planning access control wiring for a commercial building? This guide covers everything facility managers, low-voltage contractors, and security integrators need to know about powering electrified door hardware — from electric strikes and magnetic locks to electrified exit trim and card readers. We cover wire gauge selection, voltage drop calculations, power supply sizing, fail-safe vs. fail-secure wiring, fire alarm integration, and common installation mistakes that cause callbacks.

B&H Depot LLC is an authorized commercial door hardware distributor stocking over one million products from Schlage, Von Duprin, HES, Securitron, Corbin Russwin, Sargent, and other leading access control brands. We ship from 26 US warehouse locations with most orders arriving in 1–3 business days. Shop our full access control hardware catalog at KeylessAccessLocks.com.


Types of Electrified Door Hardware and Their Power Requirements

Every access control system starts at the door — and every electrified door device has specific voltage, current, and wiring requirements that must be met for reliable operation. Getting these wrong causes intermittent failures, nuisance alarms, and expensive service calls.

Device Type Typical Voltage Current Draw (Inrush / Holding) Fail-Safe or Fail-Secure Common Brands
Electric Strike 12VDC or 24VDC 0.3A–0.65A holding / up to 3A inrush Both options available HES, Von Duprin, Folger Adam, Adams Rite
Magnetic Lock (Maglock) 12VDC or 24VDC 0.25A–0.5A at 24VDC (600 lb) / up to 1A at 12VDC (1200 lb) Fail-safe only (unlocks on power loss) Securitron, SDC, DynaLock, RCI
Electrified Mortise Lock 12VDC or 24VDC 0.15A–0.4A Both options by function Schlage L9000, Corbin Russwin ML2000, Sargent 8200
Electrified Exit Trim 12VDC or 24VDC 0.2A–0.5A Both options by function Von Duprin E996L, Sargent 60-8900, Schlage Electronics
Electric Latch Retraction (ELR) 24VDC 2.5A–4A inrush / 0.15A holding Fail-secure (stays latched on power loss) Von Duprin 6211, Sargent 6300
Card Reader / Credential Reader 12VDC (some 5VDC) 0.1A–0.3A N/A — input device only HID, ASSA ABLOY, Schlage, Allegion
Request-to-Exit (REX) Sensor 12VDC or 24VDC 0.05A–0.15A N/A — sensor only Securitron, SDC, Seco-Larm

Wire Gauge Selection & Voltage Drop

Voltage drop is the #1 cause of access control failures. Low-voltage door hardware is sensitive to voltage drop over long wire runs. If the voltage at the device drops below its minimum operating threshold, the lock will not engage (or disengage) reliably. Here is how to size wire correctly.

Voltage Drop Formula

Vdrop = (2 × L × I × R) / 1000

Rule of thumb: Keep total voltage drop under 10% of source voltage. For a 12VDC system, that means no more than 1.2V drop. For 24VDC, no more than 2.4V drop.

Wire Gauge (AWG) Resistance (Ω/1000 ft) Max Distance at 0.5A / 24VDC Max Distance at 0.5A / 12VDC Typical Use
22 AWG16.1149 ft74 ftCard readers, REX sensors
18 AWG6.39376 ft188 ftElectric strikes, mag locks (short runs)
16 AWG4.02597 ft298 ftMag locks, electrified trim (medium runs)
14 AWG2.53948 ft474 ftELR exit devices, long runs, multiple devices
12 AWG1.591509 ft754 ftHigh-current devices, very long runs

Pro tip: Always use 24VDC when possible. It allows twice the wire run distance for the same voltage drop compared to 12VDC, and most modern access control hardware supports both voltages. 24VDC also reduces current draw, which means smaller wire and lower power supply cost.

Power Supply Sizing

A correctly sized power supply prevents brownouts that cause intermittent lock failures. Here is how to calculate the right supply.

Step-by-Step Sizing

  1. List every device connected to the supply (locks, readers, REX sensors, door contacts)
  2. Add up the continuous current draw (holding current for locks, operating current for readers)
  3. Add inrush current for the single highest-draw device (not all devices — they do not all fire simultaneously in most systems)
  4. Multiply total by 1.25 (25% safety margin per NEC guidelines)
  5. Select the next standard power supply size up

Example Calculation

System: 2 door office suite

24VDC total: 0.28 + 0.25 + 0.05 + 0.05 = 0.63A × 1.25 = 0.79A → use a 1A or 2A power supply

Standard sizes: Von Duprin PS873 (1A), Securitron BPS-24-1 (1A), Altronix AL600ULX (6A for multi-door).

Fail-Safe vs. Fail-Secure: When to Use Each

Characteristic Fail-Safe Fail-Secure
On power lossDoor UNLOCKSDoor stays LOCKED
Fire code requirementRequired on egress doors per IBC/NFPAAllowed on non-egress doors
When to useMain entrances, stairwells, exit paths, fire-rated openingsServer rooms, storage, drug cabinets, restricted areas
Wiring to fire alarmShunt power on alarm (door unlocks)No fire alarm tie-in needed (stays locked)
Typical devicesMag locks, fail-safe electric strikesFail-secure electric strikes, electrified mortise locks
Battery backupCritical — without it, power outage = unlocked buildingLess critical — door stays secure without power

Fire alarm integration: Per NFPA 72 and IBC, all fail-safe locks on egress paths MUST release on fire alarm activation. This is typically done by wiring the fire alarm panel's normally-closed dry contact in series with the lock's power supply. When the alarm activates, the contact opens, cutting power to the lock and releasing the door.

Fire Alarm Tie-In Wiring Diagram

The standard fire alarm release circuit for a mag lock:

  1. Power supply (+) → fire alarm relay (normally closed) → mag lock (+)
  2. Mag lock (−) → power supply (−)
  3. Fire alarm relay connected to fire panel's door-holder release circuit
  4. On alarm: relay opens → power to mag lock is cut → door releases

Important: Always use the fire alarm panel's supervised auxiliary relay — not an unsupervised relay. This ensures the fire panel monitors the circuit and reports a trouble condition if wiring is damaged.

Common Wiring Mistakes That Cause Callbacks

  1. Wrong wire gauge for the distance — #22 AWG on a 200-foot run to a mag lock. Result: lock buzzes but does not hold. Fix: use #18 or #16 AWG
  2. Undersized power supply — running 4 electric strikes off a 1A supply. Inrush from simultaneous activations trips the supply. Fix: add up all loads plus 25% margin
  3. No battery backup on fail-safe locks — power outage unlocks the entire building. Fix: use a power supply with built-in battery charger (Altronix AL600ULXPD16, Von Duprin PS914)
  4. Missing fire alarm tie-in on mag locks — code violation and life safety hazard. Fire marshal will shut you down. Fix: wire fire alarm normally-closed relay in series with every mag lock and fail-safe electric strike on egress doors
  5. 12VDC device on 24VDC supply — burns out the device immediately. Fix: always verify voltage rating before wiring. Use a 24V-to-12V converter if needed
  6. Daisy-chaining readers on the same home run — causes ground loop interference and intermittent read failures. Fix: run separate home runs (Wiegand) or use RS-485 bus architecture (OSDP)
  7. No end-of-line resistors on supervised inputs — panel cannot detect a cut or shorted wire on door contacts and REX sensors. Fix: install EOL resistors per manufacturer specs at the last device in each zone
  8. Running low-voltage wire in the same conduit as high-voltage — NEC violation and induces noise that causes false reads. Fix: maintain separation per NEC Article 725

Wiegand vs. OSDP: Reader Communication Protocols

Feature Wiegand OSDP (Open Supervised Device Protocol)
CommunicationOne-way (reader → panel)Two-way (reader ↔ panel)
EncryptionNone (credential sent in plain text)AES-128 encryption
Wire countMinimum 6 conductorsMinimum 4 conductors (RS-485)
Max distance500 ft (unreliable beyond 300 ft)4000 ft (RS-485 spec)
SupervisionNone — cannot detect tamper at readerFull line supervision — detects tamper, disconnect
Multi-dropNo — one reader per home runYes — up to 8 readers per RS-485 bus
Firmware updatesMust physically visit each readerRemote firmware update over the wire
Industry directionLegacy — being phased outCurrent standard — SIA recommended

Recommendation: Specify OSDP for all new installations. It is more secure (encrypted), easier to wire (fewer conductors, longer distances, multi-drop), and allows remote management. Wiegand is acceptable for retrofits where existing wiring must be reused.

Door Hardware Integration Checklist

Use this checklist for every access-controlled door to ensure nothing is missed during specification and installation:

Recommended Access Control Hardware by Application

Application Recommended Lock Recommended Reader Key Consideration
Office main entrance HES 1006 electric strike (fail-safe) or Securitron M62 maglock HID iCLASS SE or Schlage multi-tech reader Must release on fire alarm; ADA 5 lb max opening force
Server room / data center Schlage L9080 electrified mortise (fail-secure) HID iCLASS + keypad (dual authentication) Fail-secure; audit trail required; no fire alarm release needed
School classroom Corbin Russwin ML2000 with electrified trim (classroom lockdown function) HID iCLASS SE R10 Must allow free egress; lockdown capability from inside; ALICE/Run-Hide-Fight compliant
Hospital patient room Sargent 8200 with electrified trim (fail-safe) Proximity reader with nurse override Quiet operation; anti-ligature trim; infection control (antimicrobial finish)
Emergency exit with alarm Von Duprin 6211 ELR exit device None — egress only Must release on fire alarm; 15-second delayed egress allowed per NFPA
Parking garage entry Securitron M82 maglock (1500 lb, weather-resistant) HID long-range reader or vehicle tag Corrosion-resistant hardware; high holding force; weather-sealed
Multi-tenant lobby HES 9600 electric strike (surface-mounted, fail-safe) Intercom + reader combo (Aiphone, 2N) Visitor management integration; tenant directory; ADA compliant

Frequently Asked Questions

What wire gauge should I use for an electric strike?

For runs under 100 feet, 18 AWG is standard for electric strikes drawing under 0.5A at 24VDC. For runs over 100 feet, step up to 16 AWG. Always calculate voltage drop using the formula V = (2 × length × current × resistance per 1000 ft) / 1000 and keep the drop under 10% of source voltage.

Do magnetic locks need to be connected to the fire alarm?

Yes. Per IBC and NFPA 72, all magnetic locks on egress doors must release upon fire alarm activation. The standard method is wiring the fire alarm panel's normally-closed dry contact relay in series with the mag lock's power supply, so the door unlocks automatically when the alarm activates.

What is the difference between fail-safe and fail-secure?

Fail-safe means the door unlocks when power is lost (magnetic locks are always fail-safe). Fail-secure means the door stays locked when power is lost (many electric strikes and electrified mortise locks offer this option). Fire code requires fail-safe operation on egress paths so people can exit during a power outage.

Should I use 12VDC or 24VDC for access control hardware?

Use 24VDC whenever possible. It allows twice the wire run distance for the same voltage drop, draws less current (smaller wire), and is the standard for most modern commercial access control hardware. Use 12VDC only when a specific device requires it (some legacy readers and strikes) or when retrofitting existing 12V infrastructure.

What is OSDP and should I use it instead of Wiegand?

OSDP (Open Supervised Device Protocol) is the modern replacement for Wiegand. It offers AES-128 encryption, two-way communication, line supervision, multi-drop wiring (fewer home runs), and remote firmware updates. SIA recommends OSDP for all new installations. Use Wiegand only for retrofits where existing wiring must be reused.

How do I size a power supply for access control?

Add up the continuous current draw of all connected devices (locks, readers, sensors), add the highest single inrush current, then multiply by 1.25 for a 25% safety margin. Select the next standard power supply size above that number. For fail-safe systems, always use a supply with built-in battery backup.

Can I run access control wire in the same conduit as electrical wiring?

No. NEC Article 725 requires separation between Class 2 low-voltage wiring (access control) and power-limited or line-voltage conductors. Running them together induces electromagnetic interference that causes false reads, communication errors, and unreliable lock operation. Use separate conduit or maintain the required separation distance.

What is electric latch retraction (ELR) and when do I need it?

Electric latch retraction (ELR) is a motorized mechanism inside an exit device (panic bar) that retracts the latch bolt electrically, allowing the door to be opened without touching the bar. ELR is used when you need to remotely unlock an exit door — for example, a lobby exit that security can release from a desk, or a school entrance that unlocks on a schedule. ELR draws high inrush current (2.5–4A) so it requires 24VDC and 14 AWG wire.


About the Author: This guide was written by the commercial door hardware team at B&H Depot LLC, an authorized distributor of Schlage, Von Duprin, HES, Securitron, Corbin Russwin, Sargent, and other leading access control brands. We stock over one million commercial door hardware products and ship from 26 US warehouse locations. For product questions, technical support, or to place an order, visit KeylessAccessLocks.com or call (561) 826-6018.