Planning access control wiring for a commercial building? This guide covers everything facility managers, low-voltage contractors, and security integrators need to know about powering electrified door hardware â from electric strikes and magnetic locks to electrified exit trim and card readers. We cover wire gauge selection, voltage drop calculations, power supply sizing, fail-safe vs. fail-secure wiring, fire alarm integration, and common installation mistakes that cause callbacks.
B&H Depot LLC is an authorized commercial door hardware distributor stocking over one million products from Schlage, Von Duprin, HES, Securitron, Corbin Russwin, Sargent, and other leading access control brands. We ship from 26 US warehouse locations with most orders arriving in 1â3 business days. Shop our full access control hardware catalog at KeylessAccessLocks.com.
Every access control system starts at the door â and every electrified door device has specific voltage, current, and wiring requirements that must be met for reliable operation. Getting these wrong causes intermittent failures, nuisance alarms, and expensive service calls.
| Device Type | Typical Voltage | Current Draw (Inrush / Holding) | Fail-Safe or Fail-Secure | Common Brands |
|---|---|---|---|---|
| Electric Strike | 12VDC or 24VDC | 0.3Aâ0.65A holding / up to 3A inrush | Both options available | HES, Von Duprin, Folger Adam, Adams Rite |
| Magnetic Lock (Maglock) | 12VDC or 24VDC | 0.25Aâ0.5A at 24VDC (600 lb) / up to 1A at 12VDC (1200 lb) | Fail-safe only (unlocks on power loss) | Securitron, SDC, DynaLock, RCI |
| Electrified Mortise Lock | 12VDC or 24VDC | 0.15Aâ0.4A | Both options by function | Schlage L9000, Corbin Russwin ML2000, Sargent 8200 |
| Electrified Exit Trim | 12VDC or 24VDC | 0.2Aâ0.5A | Both options by function | Von Duprin E996L, Sargent 60-8900, Schlage Electronics |
| Electric Latch Retraction (ELR) | 24VDC | 2.5Aâ4A inrush / 0.15A holding | Fail-secure (stays latched on power loss) | Von Duprin 6211, Sargent 6300 |
| Card Reader / Credential Reader | 12VDC (some 5VDC) | 0.1Aâ0.3A | N/A â input device only | HID, ASSA ABLOY, Schlage, Allegion |
| Request-to-Exit (REX) Sensor | 12VDC or 24VDC | 0.05Aâ0.15A | N/A â sensor only | Securitron, SDC, Seco-Larm |
Voltage drop is the #1 cause of access control failures. Low-voltage door hardware is sensitive to voltage drop over long wire runs. If the voltage at the device drops below its minimum operating threshold, the lock will not engage (or disengage) reliably. Here is how to size wire correctly.
Vdrop = (2 Ã L Ã I Ã R) / 1000
Rule of thumb: Keep total voltage drop under 10% of source voltage. For a 12VDC system, that means no more than 1.2V drop. For 24VDC, no more than 2.4V drop.
| Wire Gauge (AWG) | Resistance (Ω/1000 ft) | Max Distance at 0.5A / 24VDC | Max Distance at 0.5A / 12VDC | Typical Use |
|---|---|---|---|---|
| 22 AWG | 16.1 | 149 ft | 74 ft | Card readers, REX sensors |
| 18 AWG | 6.39 | 376 ft | 188 ft | Electric strikes, mag locks (short runs) |
| 16 AWG | 4.02 | 597 ft | 298 ft | Mag locks, electrified trim (medium runs) |
| 14 AWG | 2.53 | 948 ft | 474 ft | ELR exit devices, long runs, multiple devices |
| 12 AWG | 1.59 | 1509 ft | 754 ft | High-current devices, very long runs |
Pro tip: Always use 24VDC when possible. It allows twice the wire run distance for the same voltage drop compared to 12VDC, and most modern access control hardware supports both voltages. 24VDC also reduces current draw, which means smaller wire and lower power supply cost.
A correctly sized power supply prevents brownouts that cause intermittent lock failures. Here is how to calculate the right supply.
System: 2 door office suite
24VDC total: 0.28 + 0.25 + 0.05 + 0.05 = 0.63A Ã 1.25 = 0.79A â use a 1A or 2A power supply
Standard sizes: Von Duprin PS873 (1A), Securitron BPS-24-1 (1A), Altronix AL600ULX (6A for multi-door).
| Characteristic | Fail-Safe | Fail-Secure |
|---|---|---|
| On power loss | Door UNLOCKS | Door stays LOCKED |
| Fire code requirement | Required on egress doors per IBC/NFPA | Allowed on non-egress doors |
| When to use | Main entrances, stairwells, exit paths, fire-rated openings | Server rooms, storage, drug cabinets, restricted areas |
| Wiring to fire alarm | Shunt power on alarm (door unlocks) | No fire alarm tie-in needed (stays locked) |
| Typical devices | Mag locks, fail-safe electric strikes | Fail-secure electric strikes, electrified mortise locks |
| Battery backup | Critical â without it, power outage = unlocked building | Less critical â door stays secure without power |
Fire alarm integration: Per NFPA 72 and IBC, all fail-safe locks on egress paths MUST release on fire alarm activation. This is typically done by wiring the fire alarm panel's normally-closed dry contact in series with the lock's power supply. When the alarm activates, the contact opens, cutting power to the lock and releasing the door.
The standard fire alarm release circuit for a mag lock:
Important: Always use the fire alarm panel's supervised auxiliary relay â not an unsupervised relay. This ensures the fire panel monitors the circuit and reports a trouble condition if wiring is damaged.
| Feature | Wiegand | OSDP (Open Supervised Device Protocol) |
|---|---|---|
| Communication | One-way (reader â panel) | Two-way (reader â panel) |
| Encryption | None (credential sent in plain text) | AES-128 encryption |
| Wire count | Minimum 6 conductors | Minimum 4 conductors (RS-485) |
| Max distance | 500 ft (unreliable beyond 300 ft) | 4000 ft (RS-485 spec) |
| Supervision | None â cannot detect tamper at reader | Full line supervision â detects tamper, disconnect |
| Multi-drop | No â one reader per home run | Yes â up to 8 readers per RS-485 bus |
| Firmware updates | Must physically visit each reader | Remote firmware update over the wire |
| Industry direction | Legacy â being phased out | Current standard â SIA recommended |
Recommendation: Specify OSDP for all new installations. It is more secure (encrypted), easier to wire (fewer conductors, longer distances, multi-drop), and allows remote management. Wiegand is acceptable for retrofits where existing wiring must be reused.
Use this checklist for every access-controlled door to ensure nothing is missed during specification and installation:
| Application | Recommended Lock | Recommended Reader | Key Consideration |
|---|---|---|---|
| Office main entrance | HES 1006 electric strike (fail-safe) or Securitron M62 maglock | HID iCLASS SE or Schlage multi-tech reader | Must release on fire alarm; ADA 5 lb max opening force |
| Server room / data center | Schlage L9080 electrified mortise (fail-secure) | HID iCLASS + keypad (dual authentication) | Fail-secure; audit trail required; no fire alarm release needed |
| School classroom | Corbin Russwin ML2000 with electrified trim (classroom lockdown function) | HID iCLASS SE R10 | Must allow free egress; lockdown capability from inside; ALICE/Run-Hide-Fight compliant |
| Hospital patient room | Sargent 8200 with electrified trim (fail-safe) | Proximity reader with nurse override | Quiet operation; anti-ligature trim; infection control (antimicrobial finish) |
| Emergency exit with alarm | Von Duprin 6211 ELR exit device | None â egress only | Must release on fire alarm; 15-second delayed egress allowed per NFPA |
| Parking garage entry | Securitron M82 maglock (1500 lb, weather-resistant) | HID long-range reader or vehicle tag | Corrosion-resistant hardware; high holding force; weather-sealed |
| Multi-tenant lobby | HES 9600 electric strike (surface-mounted, fail-safe) | Intercom + reader combo (Aiphone, 2N) | Visitor management integration; tenant directory; ADA compliant |
For runs under 100 feet, 18 AWG is standard for electric strikes drawing under 0.5A at 24VDC. For runs over 100 feet, step up to 16 AWG. Always calculate voltage drop using the formula V = (2 à length à current à resistance per 1000 ft) / 1000 and keep the drop under 10% of source voltage.
Yes. Per IBC and NFPA 72, all magnetic locks on egress doors must release upon fire alarm activation. The standard method is wiring the fire alarm panel's normally-closed dry contact relay in series with the mag lock's power supply, so the door unlocks automatically when the alarm activates.
Fail-safe means the door unlocks when power is lost (magnetic locks are always fail-safe). Fail-secure means the door stays locked when power is lost (many electric strikes and electrified mortise locks offer this option). Fire code requires fail-safe operation on egress paths so people can exit during a power outage.
Use 24VDC whenever possible. It allows twice the wire run distance for the same voltage drop, draws less current (smaller wire), and is the standard for most modern commercial access control hardware. Use 12VDC only when a specific device requires it (some legacy readers and strikes) or when retrofitting existing 12V infrastructure.
OSDP (Open Supervised Device Protocol) is the modern replacement for Wiegand. It offers AES-128 encryption, two-way communication, line supervision, multi-drop wiring (fewer home runs), and remote firmware updates. SIA recommends OSDP for all new installations. Use Wiegand only for retrofits where existing wiring must be reused.
Add up the continuous current draw of all connected devices (locks, readers, sensors), add the highest single inrush current, then multiply by 1.25 for a 25% safety margin. Select the next standard power supply size above that number. For fail-safe systems, always use a supply with built-in battery backup.
No. NEC Article 725 requires separation between Class 2 low-voltage wiring (access control) and power-limited or line-voltage conductors. Running them together induces electromagnetic interference that causes false reads, communication errors, and unreliable lock operation. Use separate conduit or maintain the required separation distance.
Electric latch retraction (ELR) is a motorized mechanism inside an exit device (panic bar) that retracts the latch bolt electrically, allowing the door to be opened without touching the bar. ELR is used when you need to remotely unlock an exit door â for example, a lobby exit that security can release from a desk, or a school entrance that unlocks on a schedule. ELR draws high inrush current (2.5â4A) so it requires 24VDC and 14 AWG wire.
About the Author: This guide was written by the commercial door hardware team at B&H Depot LLC, an authorized distributor of Schlage, Von Duprin, HES, Securitron, Corbin Russwin, Sargent, and other leading access control brands. We stock over one million commercial door hardware products and ship from 26 US warehouse locations. For product questions, technical support, or to place an order, visit KeylessAccessLocks.com or call (561) 826-6018.